Axial fans for dry coolers, remote radiators and air-cooled condensers – AC fans with frequency-converter control as an alternative to large EC fans.

Description

In Finland, data centres reject most of their heat through dry coolers, and with warm-water liquid cooling the dry coolers can handle the heat load without chillers for most of the year. Large axial fans are among the components with the longest lead times in this chain.

DCS supplies BVN SFG axial fans in 800 and 910 mm sizes. The three-phase AC fans can be built for frequency-converter operation down to about 30 % of nominal speed, so several fans can share one drive. Splitting each cooler into at least two fan groups on separate drives keeps the cooler running if a drive fails, and every motor gets its own protection.

For noise-sensitive sites, the eight-pole SFG 8T 910 runs at about 680 rpm. The optional ecoDiff diffuser lowers power consumption and noise at the same duty point, according to the manufacturer.

Typical use cases

  • Dry coolers for air-cooled and liquid-cooled data halls
  • Remote radiators of backup diesel and gas engines
  • Air-cooled condensers and air coils in heat-recovery and heat-pump plants
  • Spare fans and retrofits of existing coolers

Recommended fans

SFG 6T 91032,500 m³/h free blowing; 20,000 m³/h at about 160 Pa; 890–920 rpm; 1.8–2.4 kW
SFG 8T 910 (low-noise)23,900 m³/h free blowing; about 680 rpm; about 0.9 kW
SFG 6T 80021,000–27,500 m³/h free blowing, depending on version; 910–935 rpm; 1.0–2.0 kW
Supply3~400 V, 50 Hz; two-speed star/delta or frequency converter
Ambient temperature−40 °C to +60 °C (+50 °C for some versions)
EC motorsEC versions on request

See the SF cooling fan family →

Performance data is based on the manufacturer's catalogue. DCS confirms the final selection for each duty point.