Battery room and hazardous area fans

Ex-proof axial and roof fans for battery rooms, fuel stores and other areas classified as hazardous.

Description

Battery rooms must be ventilated so that gases released by the batteries cannot build up, and rooms with fuel tanks for backup generators may be classified as hazardous areas. The ventilation is designed on the basis of the battery type and the zone classification of each room.

BVN BTFM-EX tube axial fans and BRCF-EX roof fans have explosion-proof motors and non-sparking construction. The ATEX category, gas group and temperature class are confirmed for each delivery against the zone classification. For example, hydrogen released by lead-acid batteries requires equipment approved for gas group IIC.

Typical use cases

  • Battery rooms of UPS systems
  • Battery energy storage rooms
  • Fuel day-tank rooms for backup generators
  • Exhaust ventilation of other hazardous areas in technical buildings

Recommended fans

BTFM-EX tube axial fansØ 400–1,250 mm, 0.37–30 kW, approx. 3,500–115,000 m³/h, 4-pole
BRCF-EX roof fansSizes 280–800, 0.25–7.5 kW, approx. 1,000–17,000 m³/h, air up to +120 °C
Supply3~380–400 V, 50 Hz
DocumentationEU declaration of conformity and ATEX marking for each delivery

See the ex-proof fan family →

Performance data is based on the manufacturer's catalogue. DCS confirms the final selection for each duty point.